Choose the conduit and add one or more conductor groups.
Planning aid based on NEC 2023 Chapter 9, Tables 1, 4, 5, 5A and 8. Select any NEC conductor family. THHN/THWN-2 dimensions load automatically; for other constructions, enter the published area from the NEC table or wire manufacturer in the Area field. Fill limits are 53% for one conductor, 31% for two, and 40% for more than two. Verify cable assemblies, nipples and local requirements before installation.
ECSI Box Fill Calculator
NEC 314.16
Insulated conductors
Devices and fittings
Ready to calculate
0.0%
Select a box and enter the conductors, devices and fittings.
Planning aid based on NEC 2023 Table 314.16(A) and 314.16(B). The box list includes the standard metal-box dimensions in Table 314.16(A), plus a custom/marked-volume option. Device yokes count as two conductor volumes each. Internal clamps, fixture studs and hickeys use the largest conductor present. Up to four grounds count as one allowance; each additional ground adds ¼ allowance. Verify the box's marked volume and local requirements.